Formula

Basic Electrical Formulas

Volts (E):

 

Volts  =  square root of (watts x ohms)

Volts  =  watts  /  amperes

Volts  =  amperes x ohms

 

Ohms (R):

 

Ohms  =  volts  /  amperes

Ohms  =  volts²  /  watts

Ohms  =  watts  /  amperes²

 

Watts (W):

 

Watts  =  volts²  /  ohms

Watts  =  amperes² x ohms

Watts  =  volts x amperes

 

Amperes (I):

 

Amps  =  volts  /  ohms

Amps  =  watts  /  volts

Amps  =  square root of (watts  /  ohms)  

 

 

AC Motor Formulas:

 

E = voltage / I = amps / W = watts / PF = power factor / Eff = efficiency / HP = horsepower

 

 

Single Phase:

 

Current (amps) I = HP x 746 (where hp is known)
      E x Eff x PF  
         
Current (amps) I = KW x 1000 (where KW is known)
      E x PF  
         
Current (amps) I = Kva x 1000 (where Kva is known)
      E  
         
Horsepower (hp) (hp) = I x E x Eff x PF  
      746  
         
Kilowatts (KW) (KW) = I x E x PF  
      1000  
         
Kilovolt-Amps (Kva) Kva = I x E  
      1000  

 

 

Three Phase:

Current (amps) I = HP x 746 (where hp is known)
      1.73 x E x Eff x PF  
         
Current (amps) I = KW x 1000 (where KW is known)
      1.73 x E x PF  
         
Current (amps) I = Kva x 1000 (where Kva is known)
      1.73 x E  
         
Horsepower (hp) HP = 1.73 x I x E x Eff x PF (where hp is known)
      746  
         
Kilowatts (KW) WK = 1.73 x I x E x PF (where hp is known)
      1000  
         
Kilovolt-Amps (Kva) Kva = 1.73 x I x E (where hp is known)
      1000  

AC Efficiency and Power Factor Formulas:

Single Phase Efficiency: 746 x HP
  E x I x PF
   
Single Phase Power Factor: Input Watts
  V x A
   
Three Phase Efficiency: 746 x HP
  E x I x PF x 1.732
   
Three Phase Power Factor: Input Watts
  E x I x 1.732

Electrical Rules of Thumb:

Sync Speed Approx. Torque
rpm lb-ft per hp
3600 1.4
1800 3
1200 4.5
900 5.8

 

Rated Approximate Amps / hp
Voltage Single Phase Three Phase
115 10  
230 5 2.5
460   1.25
575   1

 

Note:  This information is provided as a quick reference resource and is not intended to serve as a substitute for qualified engineering assistance.  While every effort has been made to ensure the accuracy of this information, errors can occur.  As such, neither Flodraulic, any of its affiliated companies nor its employees will assume any liability for damage, injury or misapplication as result of using this reference guide.

Top